Cryogenic Fluids
Permit Holder Guideline #11
PERMIT TITLE: Cryogenic Fluids
CODE SECTION: (Virginia Statewide Fire Prevention Code): 3201.2
FEE: $150.00 (Check payable to the City of Richmond)
SCOPE: Shall obtain a permit to produce, store, use, handle, or dispense cryogenic fluids (boils below -130 F at 14.7 psi) in excess of the amounts listed on Table A below. Permits are not needed for vehicles equipped for and using cryogenic fluids as a fuel for propelling the vehicle or for refrigerating the lading.
PERMIT EXPIRATION: One (1) year from date issued.
REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:
- Mark containers and post NFPA 704 sign at entry to areas with hazardous materials.
- Have MSDS and site/floor plan (noting locations of hazardous materials, controls, spill response gear and items/areas of special concern) readily available on site and current copy filed with fire official.
- Containers, piping, valves and other appurtenances to be protected from damage and tampering; appropriately marked as to contents and function.
- Keep containers over 10 feet from air intakes, building exits, or combustible
materials.
- No containers shall be within 10 feet of air intakes, building exits or combustible materials.
- Containers and systems to have pressure release valves, easy for inspection and maintenance.
- Promptly remove, replace or repair leaking, damaged or corroded containers or systems.
- Areas with controls or potentially hazardous contact to persons to be adequately lighted.
Table A:
|
Type
|
Inside a Building
|
Outside of Building
|
|
Flammable:
|
1 gallon
|
60 gallons
|
|
Oxidizer (includes oxygen)
|
10 gallon
|
50 gallons
|
|
Inert
|
60 gallon
|
500 gallons
|
|
Physical or health hazard,(not indicated above)
|
Any amount
|
Any amount
|