Flammable Finishes / Floor Finishing
Permit Holder Guideline #19
PERMIT TITLE: Flammable Finishes / Floor Finishing
CODE SECTION: (Virginia Statewide Fire Prevention Code) 1501.2
FEE: $75.00 (Check payable to the City of Richmond)
SCOPE: Permit required for floor finishing or surface operations exceeding 350 square feet using Class I or II liquids (flash point below 140 degrees Fahrenheit).
PERMIT EXPIRATION: Operational
REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:
- Submit floor plan (showing vapor area, potential ignition sources, openings to adjoining internal areas and items/areas of concern), MSDS for liquids to be used, description of operation and safety provisions (including emergency procedures, after-hours contacts, and equipment) with document from the building's owner agreeing to such operations.
- No open flame or spark-producing devices shall be within 20 feet of spray space or vapor area (only approved electrical and heating devices allowed within spray or vapor area).
- HVAC systems (except approved ventilation) shall be off during and within 4 hours of operation.
- "No Smoking" signs shall be posted near spray space or vapor area and all safety procedures shall be enforced.
- The facility shall be closed to public during floor surfacing or finishing operations.
- Any accumulations of combustible residue shall be removed using non-sparking materials and immediately removed for proper disposal.
- At least (1) 4A-20-B: C rated portable fire extinguisher shall be located within 20 feet (towards the exit).
- Existing built-in fire protection to be maintained.