Dry Cleaning
Permit Holder Guideline #12
PERMIT TITLE: Dry Cleaning
CODE SECTION: (Virginia Statewide Fire Prevention Code) 1201.2
FEE: $75.00 (Check payable to the City of Richmond)
SCOPE: The use and storage of solvents used in dry cleaning system operations.
PERMIT EXPIRATION: ONE (1) year from date issued.
REQUIREMENTS: Permit holder agrees to abide by the Virginia Statewide Fire Prevention Code and any special stipulations noted on permit, as well as the following:
- Dry cleaning solvents shall be classified according to their flash points.
- Classification of dry cleaning plants and systems shall be classified based on the solvents used.
- Staff shall be trained for equipment or chemical emergencies.
- Dry cleaning by immersion and agitation in open vessels are prohibited.
- No solvent shall be used with a flash point below machine’s design or listing.
- Maximum 1 gallon solvents with flash point below 100 F/ 38 C at each work station; dispensed by approved safety can for spotting and pre-treating.
- A minimum of two 2-A:10B:C portable fire extinguishers shall be provided near the doors inside dry cleaning rooms containing Type II, Type III-A and Type III-B dry cleaning systems.